Usage of EnergyPlus as an FMU
=============================

Following items need to be observed when importing an FMU that contains EnergyPlus:

1. A tool that imports the FMU must start and stop the simulation at midnight. 
   [#f1]_
2. The ``Number of Timesteps per Hour`` in EnergyPlus must be equal
   to the sampling time of the FMU. For example, consider the following
   EnergyPlus IDF snippet:

   .. code-block:: text

     Timestep, 
     6;        !- Number of Timesteps per Hour

   Then, a tool that imports the FMU must synchronize it every 10 minutes.
   Otherwise, the simulation will stop with an error. [#f2]_

3. EnergyPlus contains the object ``RunPeriod``. 
   The start and end day of this object is ignored. [#f3]_ However,
   the entry ``Day of Week for Start Day`` will be used. For example, 
   consider the following IDF snippet:

   .. code-block:: text

      RunPeriod,         ! Winter Simulation
      Winter Simulation, !- Name
      1,                 !- Begin Month
      2,                 !- Begin Day of Month
      3,                 !- End Month
      31,                !- End Day of Month
      Monday,            !- Day of Week for Start Day
      Yes,               !- Use Weather File Holidays and Special Days
      Yes,               !- Use Weather File Daylight Saving Period
      No,                !- Apply Weekend Holiday Rule
      Yes,               !- Use Weather File Rain Indicators
      Yes;               !- Use Weather File Snow Indicators

   This IDF snippet declares January 2 to be a Monday. 
   Hence, if an FMU is simulated with 
   start time equal to 3 days, then the first day of the simulation
   will be Tuesday.

4. During the warm-up period and the autosizing of EnergyPlus, 
   no communication occurs between the FMU and the master program. 
   Thus, inputs from the co-simulation master program to EnergyPlus 
   remain constant during these times.
   
5. A tool that imports the FMU needs to make sure that the version of 
   EnergyPlus which has been used to export the FMU
   is (a) installed and (b) added to the ``system path environment variable``. Otherwise, 
   the simulation will fail with an error. If EnergyPlus has been properly added to the 
   ``system path environment variable``, then it can be started from any DOS prompt on 
   Windows, command shell console on Linux, or Terminal window on Mac OS by 
   typing ``RunEPlus.bat`` on Windows and ``runenergyplus`` on Linux or Mac OS. [#f4]_
   
6. A tool that imports the FMU can call the ``fmiDoStep()`` method only after all inputs 
   of the FMU are set and all outputs are got.
   
7. The simulation results are saved in a result folder which is created in the current 
   working directory. The name of the result folder is ``Output_FMUExport_xxx``, where 
   ``xxx`` is the FMU model ``instanceName`` as defined in the FMI specifications.

8. The weather file which comes along with an FMU is used to determine 
   if the year is a ``leap year``. It no weather file is included in the FMU, then the 
   assumption is that the year is not a ``leap year``.


.. rubric:: Footnotes

.. [#f1] This is because EnergyPlus requires simulation to start and end at
         midnight.
.. [#f2] This is because the External Interface in EnergyPlus synchronizes
         the data at the zone time step which is constant throughout
         the simulation. Synchronizing the
         data at the system time step would not avoid this problem because
         in EnergyPlus, the system time step cannot be smaller 
         than one minute.
.. [#f3] This is because a tool that imports an FMU has its own definition 
         of start time and stop time.

.. [#f4] This is because the FMU implements the FMI for co-simulation 
         in the `Tool Coupling <https://svn.modelica.org/fmi/branches/public/specifications/FMI_for_CoSimulation_v1.0.pdf>`_ scenario. 