# indevolt-modbus

A standalone, typed Python library for reading and controlling Indevolt energy
storage devices over Modbus. The caller supplies a `modbus_connection.ModbusUnit`
and owns the connection. Functional subsystems use `Component` fields, and
`IndevoltDevice` combines them with partial-failure reporting.

Repository: [eliaslecomte/indevolt-modbus](https://github.com/eliaslecomte/indevolt-modbus).

## Install

Requires Python 3.12 or newer. From this checkout:

```sh
pip install .
```

The package is not yet published. The release workflow builds a versioned wheel
and source archive and publishes them through PyPI Trusted Publishing.

## Read a device

Enable Modbus server mode in the Indevolt app. The documented TCP defaults are
port **8899** and unit **1**. The vendor currently describes physical RTU support
as forthcoming; the library accepts a serial unit but hardware support must be
confirmed for the installed firmware.

```python
from indevolt_modbus import IndevoltDevice

# unit comes from your modbus-connection backend/connection.
device = await IndevoltDevice.async_detect(unit)
report = await device.async_update(["inverter_real_time_data"])
for register in device.registers:
    if register.component in report.updated:
        print(register.name, device.value(register), register.unit)
```

Use typed subsystem attributes directly, for example
`device.system_info.modbus_version_7534`. Other subsystem classes are exported
from `indevolt_modbus.components`. `device.components` exposes the active models;
`REGISTERS` describes their public attributes. Values are `None` before a read
or when a known enumeration receives an unknown code.

```sh
uv sync
uv run script/query.py 192.168.1.50 --port 8899 --unit 1 --component inverter_real_time_data
uv run script/query.py 192.168.1.50 --port 8899 --raw --component system_info
```

Raw output contains unredacted device data. A full poll can take several minutes:
the library requests five seconds of spacing around Modbus messages, following
the vendor recommendation. Select the components you need. An explicit
`message_spacing` of at least one second is supported for bench testing.

## Writes

```python
register = next(r for r in device.registers if r.address == 1142)
await device.async_write(register, 20)  # Backup SoC, percent
await device.async_update([register.component])  # Read back actual state
```

Read-only fields reject writes. Numeric values must be finite integers within
the documented range, or the wire type's range where no narrower limit is
published. Packed dates/times are validated. Enumerations and protocol-version
gates are enforced by `async_write`. Power commands at 1151 and in schedule
slots use the single-unit 3600 W limit; parallel-system overrides are not exposed.
Direct component writes enforce field validation but callers should use
`async_write` for protocol-version-dependent enumeration restrictions.

## Register coverage and source decisions

[Register catalog](docs/registers.json) records all 194 explicit source rows,
plus the documented intervening load-profile and schedule points (350 entries).
344 numeric fields are implemented. Six serial fields remain catalog-only:
the source does not specify their length. No serial length or product identity
is guessed. Alarm words remain raw 32-bit integers because the source's `Value`
column does not state its bit-index convention. Multiword values use big-endian
word order, pending a real-device capture. The source does not specify a word
swap. Scales, signedness and zero-based addresses are used as published.

Register 7592 is labeled “Grid voltage” but has Hz units and a 0.01 scale; its
catalog label is preserved. The power-factor unit `Pct` and 0.001 scale are also
preserved, without assuming percent versus ratio. Capacity register 89 is not
an accumulated-energy counter. Unsupported fields are removed before polling
using protocol version register 7534. Optional/unavailable subsystems report
failures independently; temporary failures are retried on subsequent polls.

The linked vendor page contained a Markdown table, not a device YAML, when this
library was prepared. The JSON catalog is the reviewed, deterministic input to
`script/generate.py`. Source revisions are in [sources.json](docs/sources.json).
See the [vendor register table](https://docs.indevolt.com/docs/hardware/open-data/modbus-register-table/)
and [communication guide](https://docs.indevolt.com/docs/hardware/open-data/modbus/).

## Development

Layout, query helper, CI, release workflow and release procedure follow
[sofar-modbus](https://github.com/darkrain-nl/sofar-modbus). Runtime modeling uses
[modbus-connection](https://github.com/home-assistant-libs/modbus-connection).

```sh
uv sync
uv run script/generate.py
uv run ruff check --fix .
uv run ruff format .
uv run ruff check .
uv run mypy
uv run pytest
uv build
```

Two misplaced inverter fault continuation rows under grid charging were moved
to the inverter alarm catalog; grid charging uses its explicitly documented
0/1 values.

Hardware behavior has not been verified. Tests use the actual modbus-connection
mock backend; community captures are needed to resolve the documented gaps.
See [RELEASING.md](RELEASING.md) for publishing setup.

## Selective reads

After `await device.async_ensure_setup()`, `device.read_groups(register_keys)` returns
independent typed readers. Each reader covers one contiguous block of selected,
supported fields (at most 125 registers), with no undocumented gaps. Call
`await reader.async_update()` and read decoded attributes from that reader. Its
cache is independent of `device.value()` and the full subsystem caches. This lets
callers prioritize writes and fast telemetry between individual read requests
without narrowing the device's writable fields. Schedule all access through one
worker/connection and respect the device's message spacing.

### Directional AC power correction

The [vendor register table](https://docs.indevolt.com/docs/hardware/open-data/modbus-register-table/)
checked on 2026-10-15 labels **ACOutW (1284)** as `uint16`, while its
description defines directional inverter-plus-bypass power. A user hardware
capture reported raw `63609`, consistent with signed `-1927 W` (`63609 - 65536`).
The canonical catalog therefore overrides this field to `int16`, retaining the
vendor type and rationale in `source_data_type` and `type_override_reason`.
Generated decoding uses two's complement without reversing the sign.

- **174, inverter AC power:** positive = AC charging/input; negative = AC discharging/output.
- **6564, battery power:** positive = battery discharge; negative = battery charge.
- **1284, total AC power:** inverter power plus bypass power; the vendor describes
  bypass as positive for EPS and negative for a microinverter.

Registers 174 and 6564 remain signed and retain their distinct conventions.

### Presentation metadata

`Register.display_format` describes documented decimal firmware versions and
packed clock/schedule fields. Decoded protocol values remain numeric; consumers
may render them as versions or text times while retaining the original value.
This includes the forced-full-charge start time (7269), sleep times, and all
24 schedule start/end pairs. Split device date/time words are not a timestamp:
they are separate reads and carry no timezone.

The vendor table leaves the unit column blank for 7268 and 7270, but explicitly
specifies days and watts in their descriptions. The canonical catalog supplies
`d` and `W` respectively. No wire scaling or write bounds change.

Power factor (122) retains its signed 0.001 scale as a dimensionless ratio.
The vendor labels it `Pct`, but a live 0.99 reading agrees with approximately
173 W / 174 VA, not 0.99 percent. `source_unit` and `unit_override_reason`
record this discrepancy in the canonical catalog.